Soler & Palau THGT 400º/2h Axial Fan

Tubular axial fans, certified according to EN 12101-3 for operation immersed at 400 °C/2 h or 300 °C/2 h. Manufactured with a casing protected against corrosion by hot-dip galvanizing according to EN 1461. Impeller with adjustable “aerofoil” blades, dynamically balanced according to ISO 14694: G6.3.

  • icona-characteristics-motordirecte
    Direct-driven fan
  • icona-label-400
    400°C/2h certified fan
  • IP55
    IP55 Protection
  • atex
    ATEX Opctional

Main features

Motor approved S1 and S2 F400-120 and F300-120 certified motors approved for running continuously (S1) or for emergency operation (S2).

Corrosion resistance Casings formed from rolled sheet steel with a corrosion resistant hot dip galvanised finish.

Motor support Manufactured fromsheet steel with a corrosion resistant hot dip galvanised or Magnelis finish. Models from 400 to 800.

Aerodynamic motor support Aerodynamic design of the motor support to optimise airflow performances models from 900 to 1250.

Motor support (1400 and 1600 mm diameter): Welded on the fan casing. The whole assembly with a corrosion resistant hot dip galvanised finish.

Impeller dynamically balanced According to ISO 1940 standard, providing vibration free operation.

Wide blade design higher pressure Wide blade design to ensure the highest efficient airflow performances.

Terminal box External terminal box to ease the electrical connection.

Motors

Single-speed, 2- or 4-pole motors, depending on version. Two-speed 4/8-pole motors. Minimum efficiency class IE3 for power ratings of 0.75 kW or higher, and IE2 for lower power ratings. IE4 efficiency class for power ratings from 75 kW to 200 kW. Not applicable to 8-pole or two-speed motors. IP55 motors, Class H insulation.

Power supply

Three-phase 230/400V–50/60Hz up to 3 kW. Three-phase 400V–50Hz for higher power ratings and two-speed motors. Motors suitable for frequency inverter control. In emergency operation, DOL or power reduction is not required, provided the VFTM series of inverters is used and/or the requirements defined in UNE EN 12101-3 are followed. 60Hz versions available in EasyVent.

Standard ambient operating temperature

-20ºC to +40ºC.